EasyManua.ls Logo

Innotech Omni C20 - Figure 3-19: Typical Two Wire 4-20 Ma Input to Omni; Figure 3-20: Typical Thermistor Input to Omni; Figure 3-21: Typical Digital Output from Omni Using External DC Supply

Default Icon
90 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Page 51
Omni Installation Instructions
© Mass Electronics Pty Ltd 2017Chapter 3 – Electrical Installation
3-4.6.9 Typical Thermistor Input to Omni
Figure 3-20:  Typical Thermistor Input to Omni
Figure 3-21:  Typical Digital Output from Omni using External DC Supply
+
-
SENX
24VAC
0V
Typical
Thermistor
Input
Screened
Cable
3-4.6.8 Typical 4-20mA Two Wire Input to Omni
Figure 3-19:  Typical Two Wire 4-20mA Input to Omni
+
-
-
+
2
1
4-20mA
24VAC
0V
Omni
Typical
Humidity
Input
24VDC Out
24VDC
Sensor
Screened
Cable
The Omni 24VDC Suppy is an unregulated, isolated 24VDC output, ~1.5W, 65mA max, overload protected.
3-4.6.10 Typical Digital Output from Omni using External DC Supply
+
-
-
Typical Digital
Output
(External Supply)
24VAC
0V
Device Coil 12VDC
(250mA Max)
+
External
DC Supply
**Relay Coils Rated at 12 Volts DC**