Goodrive350 IP55 High-ingress Protection Series VFD Function parameter list
-139-
Function
code
Name
Description
Default
value
Modify
This value should be set according to field
conditions.
Setting range:0.0120.0%
P03.25
Pre-exciting time
Carry out motor pre-exciting during starting to
build a magnetic field inside the motor to
improve the torque characteristics of motor
during starting.
Setting range: 0.00010.000s
0.300s
P03.26
Flux-weakening
proportional gain
08000
1000
P03.27
Vector control
speed display
0: Display as per actual value
1: Display as per the set value
0
P03.28
Static friction
compensation
coefficient
0.0100.0%
0.0%
P03.29
Corresponding
frequency point
of static friction
0.50P03.31
1.00Hz
P03.30
High speed
friction
compensation
coefficient
0.0100.0%
0.0%
P03.31
Corresponding
frequency of
high speed
friction torque
P03.29400.00Hz
50.00Hz
P03.32
Torque control
enable
0:Disable
1:Enable
0
P03.33
Flux weakening
integral gain
08000
1200
P03.34
Flux-weakening
control mode
0x0000x112
Ones place: Control mode
0: Mode 0
1: Mode 1
2: Mode 2
Tens place: Compensation of inductance
saturation coefficient
0: Enable
1: Disable
Hundreds place: Reserved
0: Reserved
1: Reserved
0x000