Table 37: Parts Required for Connecng an EX Series Switch to Earth Ground
(Connued)
Switch Earthing
Terminal
Locaon
Grounding
Cable
Requirements
Grounding Lug
Specicaons
Screws and
Washers
Addional
Informaon
EX8208 Le side of
the chassis
6 AWG
(13.3 mm²),
minimum 90° C
wire, or as
permied by
the local code
Panduit LCD2-14A-
Q or equivalent
—provided
Two ¼ -20
x 0.5 in.
screws with
#¼” split-
washer
—provided
Two #¼” at
washers—
provided
EX8216 Two earthing
terminals:
Le side
of the
chassis
Rear
panel of
the
chassis
NOTE: You
must use
only one of
the two
protecve
earthing
terminals.
2 AWG
(33.6 mm²),
minimum 90° C
wire, or as
permied by
the local code
Panduit LCD2-14A-
Q or equivalent
—provided
Two ¼ -20 x
0.5 in.
screws with
#¼” split-
washer
—provided
Two #¼” at
washers—
provided
137