Table 37: Parts Required for Connecng an EX Series Switch to Earth Ground
(Connued)
Switch Earthing
Terminal
Locaon
Grounding
Cable
Requirements
Grounding Lug
Specicaons
Screws and
Washers
Addional
Informaon
EX9204,
EX9208,
and
EX9214
Rear panel of
the chassis
One 6 AWG
(13.3 mm²),
minimum 90° C
wire, or one
that complies
with the local
code
Thomas& Bes
LCN6-14 or
equivalent—
provided
Two ¼ -20
x 0.5 in.
screws with
#¼” split-
washer—
provided
Two #¼” at
washers—
provided
See Grounding
Cable and Lug
Specicaons for
EX9200 Switches.
EX9251 Rear panel of
the chassis
12 AWG
(2.5 mm²),
minimum 90° C
wire, or one
that complies
with the local
code—
not provided
Panduit
LCD10-10A-L or
equivalent—
not provided
Two 10-32
screws—
provided
See Grounding
Cable and Lug
Specicaons for
EX9200 Switches.
EX9253 Right side of
the chassis
14-10 AWG
(2-5.3 mm²),
minimum 90° C
wire, or one
that complies
with the local
code—
not provided
Panduit
LCD10-14B-L or
equivalent—
provided
Two M5 Pan
Head screws—
provided
Tools required for connecng an EX Series switch to earth ground:
An electrostac discharge grounding strap (provided)
A Phillips (+) number 2 screwdriver to ghten the screws.
An AC–powered EX Series switch gains addional grounding when you plug the power supply in the
switch into a grounded AC power outlet by using an AC power cord appropriate for your geographical
locaon.