However, if you need to convert a QFX5110 to have a different airflow, you can change
the airflow pattern. To convert an AIR IN product SKU to an AIR OUT product SKU or an
AIR OUT product SKU to a AIR IN product SKU, you must replace all of the fans and power
supplies at one time to use the new direction. The system raises an alarm when the
system is converted, which is normal.
Related
Documentation
QFX5110 Field-Replaceable Units on page 15•
• Prevention of Electrostatic Discharge Damage on page 182
• QFX5110 Hardware Overview on page 3
• Installing a Fan Module in a QFX5110 on page 105
• Removing a Fan Module from a QFX5110 on page 106
QFX5110 Fan Module LED
Figure 14 on page 30 shows the location of the LED next to the fan module.
Figure 14: Fan Module LED in a QFX5110 Switch
g050487
CO
CON
ALM
SYS
MST
ID
RESET
CO
1
1— Fan LED
Table 13 on page 30 describes the function of the fan tray LED.
Table 13: Fan Tray LED in a QFX5110 Switch
DescriptionStateColorName
The fan module is operating normally. The system
has verified that the module is engaged, that the
airflow is in the correct direction, and that the fan is
operating correctly.
On steadilyGreenFan
An error has been detected in the fan module.
Replace the fan module as soon as possible. Either
the fan has failed or it is seated incorrectly. To
maintain proper airflow through the chassis, leave
the fan module installed in the chassis until you are
ready to replace it.
BlinkingAmber
Under normal operating conditions, the fan modules operate at a moderate speed.
Temperature sensors in the chassis monitor the temperature within the chassis.
Copyright © 2017, Juniper Networks, Inc.30
QFX5110 Switch Hardware Guide