10. Averaging period of min/max P and Q
The averaging period used in the calculation of minimum and maximum values of power (P) and flow (Q) can be
adjusted. The averaging period is stated in minutes. Read more about the averaging period of min./max. of P and Q
in paragraph 7.5.
11. Heat/cooling shift (θ
hc
)
The limit (θ
hc
) for heat/cooling shift can be adjusted in ”SETUP loop”, however only in meters ordered as meter type
6 (heat/cooling meter). The value can be set in the interval 2…180,00 °C as well as at 250,00 °C if the user wants to
disable the function. The function can be enabled again by setting the limit at a value in the valid area of 2…180 °C.
Heat/cooling shift is permanently disabled in other meter types, and ”Off” will thus be displayed for this reading in all
other meter types than 6. Read more about heat/cooling shift in paragraph 7.4.
Meter type: 1, 2, 3, 4, 5, 7
The frames around ”Off” will be shown
as long as the secondary key remains
activated.
The first digit flashes and each digit can
now be set at a value between 0 and 9.
If you choose a value outside the valid
interval (2…180,00 °C) the value is
automatically adjusted to 250,00 °C,
which indicates that the function has
been switched off.