MULTICAL® 403
Kamstrup A/S · Technical description · FILE100000166_B_EN-55121689_M1_07.2023
7.1.4 Energy calculations
MULTICAL
403 calculates energy on the basis of the formula stated in EN 1434-1, which uses the international
temperature scale issued in 1990 (ITS-90) and the pressure definition of 16 bar.
In a simplified form the energy calculation can be expressed as: Energy = V x ∆Θ x k. The calculator always calculates
energy in [Wh], and then converts the value to the selected measuring unit.
E [Wh] =
V x
Θ x k x 1000
E [kWh] = E [Wh] / 1,000
E [MWh] = E [Wh] / 1,000,000
E [GJ] = E [Wh] / 277,800
V is the added (or simulated) water volume in m
3
∆Θ is the measured temp. difference: Heat energy (E1) ∆Θ = inlet temperature less outlet temperature
Cooling energy (E3) ∆Θ = outlet temperature less inlet temperature
Both in the display and during data reading each energy type is uniquely defined e.g.
Heat energy: E1 = V1(t1-t2)k
Cooling energy: E3 = V1(t2-t1)k
k is the heat coefficient of water, calculated according to the formula of EN 1434 and OIML R75-1:2002
Kamstrup A/S can supply an energy calculator for check measurement:

Table of Contents

Other manuals for Kamstrup MULTICAL 403

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Kamstrup MULTICAL 403 and is the answer not in the manual?

Kamstrup MULTICAL 403 Specifications

General IconGeneral
TypeUltrasonic Heat Meter
Flow SensorUltrasonic
Pressure RatingPN16
Battery LifeUp to 16 years
ApprovalMID Class 2
DisplayLCD
CommunicationM-Bus, Wireless M-Bus, Modbus, BACnet
Power SupplyBattery
AccuracyClass 2
Protection ClassIP54
Housing MaterialComposite
Flow Rate Range0.6 m3/h to 15 m3/h

Related product manuals