EasyManua.ls Logo

Keysight E4990A - Page 272

Keysight E4990A
669 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
E4990A Help
262
Analyzer.WriteString ":SENS1:CORR1:COLL:ACQ:SHOR", True
' Wait for measurement to end
Analyzer.WriteString "*OPC?", True
Dmy = Analyzer.ReadNumber
MsgBox "Connect LOAD Termination"
' Execute load in user calibration
Analyzer.WriteString ":SENS1:CORR1:COLL:ACQ:LOAD", True
' Wait for measurement to end
Analyzer.WriteString "*OPC?", True
Dmy = Analyzer.ReadNumber
' Save impedance setup data
Analyzer.WriteString ":SENS1:CORR1:COLL:SAVE", True
MsgBox "Impedance Setup Done"
' Close IO
Analyzer.IO.Close
End Sub
Fixture Compensation
Overview
Sample Program in Excel VBA
Other topics about Preparing for Accurate Measurement
Overview
The program listed in the below section is written in VISA-COM with Excel
VBA. It can be executed from the external PC controller. The program
demonstrates how to perform fixture compensation.
Fixture Compensation Sample Program in Excel VBA
' The memory area of the resource manager and the instrument I/O are acquired
Dim iomgr As VisaComLib.ResourceManager
Dim Analyzer As VisaComLib.FormattedIO488
Sub FixtureCompen()
Dim Dmy As Integer, Flg As Integer
Set iomgr = New VisaComLib.ResourceManager
Set Analyzer = New VisaComLib.FormattedIO488
' Open the instrument. Set the GPIB address.

Table of Contents

Other manuals for Keysight E4990A

Related product manuals