EasyManua.ls Logo

Kidde ARIES

Kidde ARIES
282 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
August 2013 3-40 P/N 06-236530-001
3-2.5.2.4.10 How to Change a Photoelectric Detector's Supervisory Alarm Threshold
Purpose: To change the alarm threshold of one or more photoelectric
detectors reporting as supervisory initiating devices. The photoelectric
detector can be programmed to report a supervisory condition
anywhere within the obscuration range of 0.5 to 3.5 percent per foot
when used in an open-area application. Supervisory alarm thresholds
can be set in 0.1 percent-per-foot increments. One additional
supervisory-reporting range is defined for a special application. The in-
duct/DH-2000 range refers to detector placement in a DH-2000 Duct
Housing with associated sampling tubes to monitor the air in either a
supply- or return-air duct or to detector placement in a duct. The
supervisory-alarm range for this special application is 0.5 to 2.0
percent per foot.
CAUTION
This application is not UL Listed or FM Approved
Step Action Result
1 Press 0 Key Initiate menu access
2 Enter Password; Press “Enter” Key Gain access to menus
3 Press 3 Key Enter Set-Menu branch
4 Press 3 Key Access "SLC Devices" option
5 Press 2 Key Select "Configuration"
6 Press 2 Key Select Photoelectric Detectors
7 Press 2 Key Select supervisory threshold
8 Use keypad to enter single detector or range of
detectors to change supervisory alarm threshold.
Press "Enter" Key to confirm selection
Specify detectors to change
9 Press 1 Key for Open Area or
Press 2 Key for In-duct/DH-2000
Press "Enter" Key to confirm selection.
Specify detector application
10 Press 1 Key for “Fixed” or Press 2 Key for
“Day/Night” settings.
Press “Enter” Key to confirm selection
Select fixed (i.e., not variable) thresholds or
select day/night (i.e., variable by the time of day)
thresholds
11 Use keypad to enter supervisory-alarm threshold.
Press "Enter" Key to confirm selection.
Set supervisory-alarm threshold. This is the day
alarm threshold when using day/night settings.
11A Use keypad to enter night supervisory-alarm
threshold. Press “Enter” Key to confirm selection.
Set night supervisory-alarm threshold (day/night
only).
12 Wait until "Updated Thresholds for Devices xx"
message disappears from the display.
13 Press "Backspace" Key (as required) Exit Menu System

Table of Contents

Related product manuals