P/N 06-236530-001 3-39 August 2013
Step Action Result
1 Press 0 Key Initiate menu access
2 Enter Password; Press “Enter” Key Gain access to menus
3 Press 3 Key Enter Set-Menu branch
4 Press 3 Key Access "SLC Devices" option
5 Press 2 Key Select "Configuration"
6 Press 2 Key Select Photoelectric Detectors
7 Press 1 Key Select alarm thresholds
8 Press 1 Key for Fixed or Press 2 Key for Day/Night
Settings.
Select fixed (i.e., not variable) thresholds or
select day/night (i.e. variable by time of day)
thresholds
9 Use keypad to enter single detector or range of
detectors to change pre-alarm/alarm thresholds.
Press "Enter" Key to confirm selection
Specify detectors to change
10 Press 1 Key for Open Area or
Press 2 Key for In-duct or
Press 3 Key for DH-2000
Press "Enter" Key to confirm selection.
Specify detector application
11 Use keypad to enter pre-alarm threshold.
Press "Enter" Key to confirm selection.
Set pre-alarm threshold
12 Use keypad to enter alarm threshold.
Press "Enter" Key to confirm selection.
Set alarm threshold. This is the day alarm
threshold when using day/night settings.
12A Use keypad to enter night alarm threshold.
Press “Enter” Key to confirm selection.
Set night alarm threshold (day/night only)
13 Wait until "Updated Thresholds for Device x"
message disappears from the display.
14 Press "Backspace" Key (as required) Exit Menu System