P/N 06-236530-001 3-57 August 2013
3-2.5.2.4.32 How to De-Activate Positive-Alarm Sequence for Smoke Detectors
Purpose: To de-activate positive-alarm sequence for one or more
smoke detectors. See Paragraph 3-2.5.5.1 for the description of
positive-alarm sequence.
3-2.5.2.4.33 How to Clear the System Event Log
Purpose: To remove all previously recorded system events from the
ARIES event log.
Step Action Result
1 Press 0 Key Initiate menu access
2 Enter Password; Press “Enter” Key Gain access to menus
3 Press 3 Key Enter Set-Menu branch
4 Press "Scroll" Key Access additional options
5 Press 4 Key Select Programming option
6 Press "Scroll" Key Access additional options
7 Press 6 Key Select "Positive-Alarm Sequence"
8 Press 2 Key and then press "Enter" Key to confirm
selection.
De-activate positive-alarm sequence
9 Use keypad to enter single address or range of
smoke-detector addresses for PAS to be de-
activated.
Press "Enter" Key to confirm selection.
Specify addresses for positive-alarm sequence to
be de-activated
10 Press "Backspace" Key (as required) Exit Menu System
11 Wait until "Initializing Configuration" message
disappears from the display.
Resume Normal Operations
Step Action Result
1 Press 0 Key Initiate menu access
2 Enter Password; Press “Enter” Key Gain access to menus
3 Press 3 Key Enter Set-Menu branch
4 Press "Scroll" Key Access additional options
5 Press 4 Key Select Programming option
6 Press "Scroll" Key twice Access additional options
7 Press 7 Key Select "Clear Events"
8 Press 1 Key and then press "Enter" Key to confirm
selection.
Select and clear system event log
9 Wail until “Event Log Clear in Progress” message
disappears from the display.
10 Press "Backspace" Key (as required) Exit Menu System