August 2013 3-58 P/N 06-236530-001
3-2.5.2.4.34 How to Clear the Contents of the SLC-Initiating Devices Test Log
Purpose: To remove the most-recently recorded results of initiating
devices tests from the SLC Test Log. All initiating devices are tested
once per day to confirm that they can transmit an acceptable event-
detection signal. The results of the most-recently-transmitted event
signal are recorded in the SLC Test Log.
3-2.5.2.4.35 How to Clear the Contents of the Walk-Test Log
Purpose: To remove the most-recently recorded results of initiating-
devices walk tests from the Walk-Test Log. The results of the most-
recently-conducted walk tests are recorded in the Walk-Test Log.
Step Action Result
1 Press 0 Key Initiate menu access
2 Enter Password; press “Enter” Key Gain access to menus
3 Press 3 Key Enter Set-Menu branch
4 Press "Scroll" Key Access additional Set-Menu options
5 Press 4 Key Select Programming option
6 Press "Scroll" Key twice Access additional Programming-Menu options
7 Press 8 Key Select "Clear Tests" option
8 Press 1 Key Select “Clear SLC Tests”
9 Enter starting SLC address and ending SLC
address.
Use XXX format for addresses.
Press “Enter” Key to confirm address range to
clear.
Specify range of SLC initiating devices to have
test results cleared
10 Press "Backspace" Key (as required) Exit Menu System
Step Action Result
1 Press 0 Key Initiate Menu Access
2 Enter Password; press "Enter" Key Gain access to menus
3 Press 3 Key Enter Set-Menu branch
4 Press "Scroll" Key Access additional Set-Menu options
5 Press 4 Key Select "Programming" option
6 Press "Scroll" Key twice Access additional Programming-Menu options
7 Press 8 Key Select "Clear Tests" option
8 Press 2 Key Select “Clear Walk Tests”
9 Enter starting SLC address and ending SLC
address.
Use XXX format for addresses.
Press "Enter" Key to confirm address range to
clear.
Specify range of SLC initiating devices to have
walk-test results cleared
10 Press "Backspace" Key (as required) Exit Menu System