P/N 06-236530-001 3-59 August 2013
3-2.5.2.4.36 How to Resynchronize the Network
Purpose: To restore uniformity of event display among the members of
a networked ARIES system.
3-2.5.2.4.37 How to Activate Global Acknowledge
Purpose: To enable the "Acknowledge" Switch to process any
combination of up to 30 unacknowledged supervisory or trouble
events.
Step Action Result
1 Press 0 Key Initiate menu access
2 Enter Password Gain access to menus
3 Press 3 Key Enter Set-Menu branch
4 Press "Scroll" Key Access additional options
5 Press 4 Key Select Programming option
6 Press "Scroll" Key twice Access additional options
7 Press 9 Key Select "Resynchronize Network"
8 Press "Backspace" Key (as required) Exit Menu System
Step Action Result
1 Press 0 Key Initiate menu access
2 Enter Password; Press “Enter” Key Gain access to menus
3 Press 3 Key Enter Set-Menu branch
4 Press "Scroll" Key Access additional options
5 Press 5 Key Select “Globals”
6 Press 1 Key Select "Global Acknowledge"
7 Press 1 Key and then press "Enter" Key to confirm
selection.
Activate global acknowledge
8 Press "Backspace" Key (as required) Exit Menu System

Table of Contents