August 2013 3-106 P/N 06-236530-001
The following actions also occur when an alarm verification is reported:
• The internal buzzer pulses
• The alarm verification event is stored in the event log
• The alarm verification message is transmitted to peripheral devices
such as RDCMs, if applicable
• The alarm verification message is communicated via the RS-232
ports
3-2.5.5.4 What to Do When Alarm Verification Occurs
Press the <ACKNOWLEDGE> Key to silence the internal buzzer. The
display will change to the appearance in Figure 3-20. Acknowledgments of
alarm verifications are logged.
Figure 3-20. Alarm Verification Acknowledgment Message
The upper line of the LCD display shows the verification time remaining to
receive an alarm confirmation signal from the smoke detector. The
verification time will continually decrease in one-second intervals. The
control unit will return to Normal Mode if the smoke detector does not
reconfirm the alarm condition or if no other alarm-initiating device reports
at any time prior to the expiration of the verification period. A verification
off event is stored in the event log if neither an alarm reconfirmation nor
a secondary-alarm message is reported.
3-2.5.6 SUPERVISORY STATE
The ARIES Control Unit enters the Supervisory State when an initiating event
occurs such as a monitor module report of a low-air-pressure condition in a pre-
action-sprinkler system. It also occurs when any SLC-based initiating or control
device, an IIM initiating device, or any control unit based output circuit, is
isolated.
The upper line of the LCD display shows the supervisory event by the device
address, the state change, and the device type. The lower line indicates the up-
to-40-character message assigned to the supervisory device using the ARIES
configuration program.
Figure 3-21. Typical Supervisory Message Display
010 ALARM VERIFY PHOTOELECTRIC 60 SEC
CONTROL ROOM
Alarm-Verification Indication On (Smoke Detectors only)
Device Type Reporting
Alarm-Verification On
Device Address 010
Device-Specific
Custom Message
Time Remaining for
Alarm Verification
070 SUPERVISORY ON MONITOR MODULE
FIFTH-FLOOR GATE VALVE
Supervisory On Indication
Device Type
Device Address 070
Device-Specific
Custom Message