EasyManua.ls Logo

Kidde ARIES

Kidde ARIES
282 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
P/N 06-236530-001 1-19 August 2013
1-7.4 Notification-Appliance and Releasing Circuits
All circuits are power-limited except where noted.
1-7.5 Relays
The three programmable relays and the trouble relay can be used for either power-
limited or non-power-limited circuits. Contact ratings for these relays are:
1.0 A @ 30 Vdc (resistive)
0.5 A @ 30 Vdc (inductive)
0.5 A @ 120 Vac (inductive).
1-7.6 Auxiliary Outputs
The auxiliary outputs are power limited.
Operating Voltage Range: 18.8 - 27.6 Vdc
Maximum Current: 1.0A (each circuit)
Maximum Current for all external devices: 5.0A
Note: External devices include notification appliances, releasing solenoids, SLC initiating
and control devices, and all devices powered from the 24 Vdc Auxiliary
Power Terminals (TB 2). All applicable compatible devices contained in this
manual may be used.
NAC Rating Regulated 24 Vdc
NAC Wiring Class A, Style Z
Class B, Style Y
Note: NACs suitable for synchronized and non-synchronized notification appliances.
Use polarized notification appliances only. The maximum number of
synchronized devices is 25.
Max. Wiring Voltage Drop: 2 V (for NACs)
Varies (for Releasing Circuits)
Refer to Paragraph 2-9 through
Paragraph 2-11
Operating Voltage: 24 Vdc (nominal)
Max. NAC Current: 1.5 A
Max. Rel. Ckt. Current: 2.4 A
Max. Current for all external devices: 5.0 A
Note: External devices include notification appliances, releasing solenoids, SLC
initiating and control devices, and all devices powered from the 24 Vdc
Auxiliary-Power Terminals (TB 2).
NAC End-of-Line Resistor: 10 K, 0.5 W
Releasing Circuits: Releasing circuits are not power-limited when
actuators are used or when In-Line Device is
not used for solenoid valves
Use In-Line Device, P/N 06-220023-001, to
make a single-solenoid or dual-solenoid
releasing circuit power-limited