August 2013 3-56 P/N 06-236530-001
3-2.5.2.4.30 How to De-Activate Alarm Verification for Smoke Detectors
Purpose: To de-activate alarm-verification for one or more smoke
detectors. See Paragraph 3-2.5.5.3 for the description of alarm
verification.
3-2.5.2.4.31 How to Activate Positive-Alarm Sequence for Smoke Detectors
Purpose: To activate positive-alarm sequence for one or more smoke
detectors. See Paragraph 3-2.5.5.1 for the description of positive-
alarm sequence.
Step Action Result
1 Press 0 Key Initiate menu access
2 Enter Password; Press “Enter” Key Gain access to menus
3 Press 3 Key Enter Set-Menu branch
4 Press "Scroll" Key Access additional options
5 Press 4 Key Select Programming option
6 Press "Scroll" Key Access additional options
7 Press 5 Key Select "Alarm-Verification" option
8 Press 2 Key and then press "Enter" Key to confirm
selection.
De-activate alarm verification
9 Use keypad to enter single address or range of
smoke-detector addresses for verification to be
de-activated.
Press "Enter" Key to confirm selection.
Specify addresses for verification to be de-
activated
10 Press "Backspace" Key (as required) Exit Menu System
11 Wait until "Initializing Configuration" message
disappears from the display.
Resume Normal Operations
Step Action Result
1 Press 0 Key Initiate menu access
2 Enter Password; Press “Enter” Key Gain access to menus
3 Press 3 Key Enter Set-Menu branch
4 Press "Scroll" Key Access additional options
5 Press 4 Key Select Programming option
6 Press "Scroll" Key Access additional options
7 Press 6 Key Select "Positive-Alarm Sequence"
8 Press 1 Key and then press "Enter" Key to confirm
selection.
Activate positive-alarm sequence
9 Use keypad to enter single address or range of
smoke-detector addresses for positive-alarm
sequence.
Press "Enter" Key to confirm selection.
Specify addresses for Positive-Alarm Sequence
10 Press "Backspace" Key (as required) Exit Menu System
11 Wait until "Initializing Configuration" message
disappears from the display.
Resume Normal Operations