August 2013 3-84 P/N 06-236530-001
3-2.5.2.5.4 How to End Walk Test
Purpose: To terminate a walk test.
Note: The walk-test mode will automatically end after 30 minutes of
inactivity. It can also be stopped by a system reset.
3-2.5.2.5.5 How to Activate a Fire Drill
Purpose: To manually activate one or more NACs and/or control
modules that are programmed for operation during a fire drill.
Note: Each NAC or control module must be programmed for drill
operation via the ARIES Configuration Program. The fire drill
must be ended via a menu operation or a system reset before
the system can be returned to normal operating condition.
3-2.5.2.5.6 How to End a Fire Drill
Purpose: To manually conclude a fire drill.
Step Action Result
1 Press 0 Key Initiate menu access
2 Enter Password; Press “Enter” Key Gain access to menus
3 Press 4 Key Enter Test-Menu branch
4 Press 5 Key Select "Walk Test" option
5 Press 2 Key End walk test
6 Press "Backspace" Key (as required) Exit Menu System
Step Action Result
1 Press 0 Key Initiate menu access
2 Enter Password; Press “Enter” Key Gain access to menus
3 Press 4 Key Enter Test-Menu branch
4 Press 5 Key Select "Fire Drill"
5 Press 1 Key, then Press “Enter” Key Initiate fire drill
6 Press "Backspace" Key (as required) Exit Menu System
Step Action Result
1 Press 0 Key Initiate menu access
2 Enter Password; Press “Enter” Key Gain access to menus
3 Press 4 Key Enter Test-Menu branch
4 Press 2 Key Select "Fire Drill"
5 Press “Enter” Key Stop fire drill
6 Press "Backspace" Key (as required) Exit Menu System