August 2013 3-92 P/N 06-236530-001
3-2.5.2.5.15 How to De-Activate Remote Release Modules
Purpose: To manually de-activate one or more RRMs that were
activated during system testing.
Note: Each RRM must be manually de-activated via this menu
operation or a system reset before the system can be returned
to normal operating condition.
Step Action Result
1 Press 0 Key Initiate Menu Access
2 Enter Password; press "Enter" Key Gain access to menus
3 Press 4 Key Enter Test-Menu branch
4 Press "Scroll" Key Access additional Test-Menu options
5 Press 7 Key Select "Output Test" option
6 Press "Scroll" Key twice Access additional Outputs-Test options
7 Press 9 Key Select "RRM Group"
8 Press 1 Key and then press "Enter" Key Activate “RRM Group Devices”
9 Press 1, 2, 3 or 4 Key for the RRM group and then
press "Enter" Key.
Select the applicable RRM group.
10 De-activate all control modules after confirming
proper operation
See Paragraph 3-2.5.2.5.15
11 Press "Backspace" Key (as required) Exit Menu System
CAUTION
There is no indication at the control unit that an output is activated. Be sure to
de-activate the output after proper operation has been confirmed.
Ensure that the remote release modules are not activating suppression
systems. Physically disconnect the wiring to all agent-release and pre-action-
sprinkler circuits if the control modules are activating suppression systems.
Restore the system to normal operating condition at the conclusion of all RRM
activations and any other functional tests.