P/N 06-236530-001 3-121 August 2013
Figure 3-48. Typical Device Not Registered Message
4. Wait for all of the device-not-registered troubles to report. Press the
<ACKNOWLEDGE> Key one or more times to silence the control unit buzzer.
5. Confirm that no more trouble messages have been reported.
6. Record the number of currently-active troubles. The number of troubles
should be equal to the number of SmartOne devices connected to the SLC.
7. Run the AutoLearn Routine as follows:
a. Press the 0 Key. This display will show this message:
Figure 3-49. Password Prompt
b. Press the default Level-2 Password keys (186591) and then press the
<Enter> Key. The top-level menu selections will be displayed:
Figure 3-50. Top-Level Menu Selections
c. Press the 3 Key to select "SET"
Figure 3-51. Set Menu
d. Press the <SCROLL> Key and then the 4 Key to select
"PROGRAMMING"
Figure 3-52. Additional Set-Menu Selections
e. Press 3 to select "AUTOLEARN"
Figure 3-53. Programming Sub-Menu
Figure 3-54 shows a typical message that displays when the AutoLearn
routine is running.
205 NOT REGISTERED ON UNKNOWN TYPE
UNUSED SLC DEVICE
Trouble Not-Registered Indication
Device Type Not Known
at This Time
Device Address 205
PLEASE ENTER PASSWORD
******
1: ISOLATE 2: LIST
3: SET 4: TEST
1: TIME/DATE 2: PORT CONTROL
3: SLC DEVICES SCROLL FOR MORE
4: PROGRAMMING 5: GLOBALS
6: NETWORK (FUTURE) SCROLL FOR MORE
1: DAY/NIGHT 2: PASSWORDS
3: AUTOLEARN SCROLL FOR MORE