P/N 06-236530-001 4-3 August 2013
Figure 4-1. Device/Circuit Assignments
Device/Circuit Assignments
Head-End Room (Zone 1)
Photoelectric Detectors
Ionization Detectors
Manual Release Stations
Abort Switches
Audible NAC
Visible NAC
Waterless Extinguishing System Release Circuit
Pre-Action-Sprinkler Release Circuit
Power Room (Zone 2)
Photoelectric Detectors
Ionization Detectors
Manual Release Stations
Abort Switches
Audible NAC
Visible NAC
Waterless Extinguishing System Release Circuit
Pre-Action-Sprinkler Release Circuit
Facility Equipment Interlocks
HVAC Shutdown
Power Shutoff
Off-Premises Reports
Major Alarm to Central Station
Critical Alarm to Central Station
Waterflow Alarm to Central Station
Pre-Action-Valve to Central Station
Supervisory to Central Station
Trouble to Central Station
SLC Device Addresses
Photoelectric
Detectors
1-5 15-
18
Ionization Detectors 6-
10
19-
21
Monitor Modules 11-
12
13-
14
22 23
Control Modules 24 25 26 27
Control-Unit Outputs
NAC 1 X
NAC 2 X
Combo 1 X
Combo 2 X
Release 1 X X
Release 2 XX
Relay 1 X
Relay 2 X
Relay 3 X
Troub le Relay X