Chapter 3: System operation
P/N 3102352-EN • REV 005 • ISS 28DEC18 145
Conducting a lamp test
A lamp test lights all of the LEDs on the panel and the LED annunciator and tests the LCD so
that you can verify proper operation. LEDs stay on for 15 seconds.
To conduct a lamp test:
1. Press the Lamp Test button on the front panel.
2. Verify that the LCD, all LEDs on the panel, and LED annunciators (if used) work properly.
Notes
• Pressing the Lamp Test button does not perform a lamp test on remote annunciators. To
perform a lamp test on remote annunciators, press the Lamp Test button on the remote
annunciator.
• You can also initiate a lamp test from the test menu.
Activating and restoring output devices
Activating an output device on a signaling line circuit (SLC) turns on its output. This is typically
done to test individual strobes, horns, and other notification appliances. Restoring the device
turns it off again.
Notes
• Input devices cannot be activated. If you attempt to activate an input device, the message
“Invalid device” is displayed.
• Disabled devices must be manually enabled and then restored. See “Activating and
restoring sensor bypass” on page 147.
• Latched outputs must be manually unlatched and then restored. See “Unlatching latched
output device” on page 146.
To activate or restore an output device:
1. Press the Menu button and choose Control.
2. Enter a level one password.
3. Choose Activate/Restore.
4. Choose Device.
5. Choose the loop the device is on.
Note: If the panel only has one loop, the loop selection screen does not display.
6. Enter the device ID for the device that you want to activate or restore.