Chapter 3: System operation
152 P/N 3102352-EN • REV 005 • ISS 28DEC18
To disable or enable a panel event:
1. Press the Menu button and choose Control.
2. Enter a level one password.
3. Choose Enable/Disable.
4. Choose Panel Event.
5. Enter the ID number of the event type to disable or enable.
See “Event ID numbers and descriptions” on page 137 for event descriptions and the list
above for the events that can be disabled.
6. Press Enter.
7. Press Cancel to return to the previous menu.
— or —
Press the Menu button to exit menu mode.
When you disable an event:
• The common Disable LED turns on
• The common Trouble LED flashes and the panel goes into a trouble state
• The common Trouble relay changes state
• The disabled and active points indicators on the LCD increment
• The LCD displays a message indicating that the event is disabled.
Disabling and enabling loop events
Disabling a loop event prevents it from being displayed, printed, or reported off premises. This
is typically done during maintenance. For example, you might want to disable the Loop 1
unconfigured alarm event, if you are switching out a detector. Remember to enable the event
as soon as you have finished working.
When you disable a loop event:
• The common Disable LED turns on
• The common Trouble LED flashes and the panel goes into a trouble state
• The common Trouble relay changes state
• The disabled and active points indicators on the LCD increment.
• The LCD displays a message indicating which loop event is disabled.
Not all events can be disabled. Those that cannot are labeled as “forbidden.” The following
table lists events that can be disabled.