Appendix C: Applications
218 P/N 3102352-EN • REV 005 • ISS 28DEC18
CO alarm, CO supervisory, and CO monitor signals do not activate TC3 fire evacuation
signals.
Correlated zone and system alarm signaling
applications
Correlated signaling applications are those in which sounder bases are triggered by associated
correlation groups. This includes zone alarm and system alarm signaling applications.
Detectors are added to the input side, and polarity reversal modules are added to the output
side of one or more correlation groups.
Zone alarm signaling applications
What is zone alarm signaling?
In zone alarm signaling applications, detectors and sounder bases are grouped by zone. All
sounder bases within a zone automatically sound alarm signals when any detector in the zone
initiates an alarm event.
The sounder bases, once activated, continue to sound an alarm signal until:
Smoke is cleared from the active detectors and the control panel is reset.
Signal Silence is pressed.
The control panel’s Auto Signal Silence timer expires, if programmed. This can be from 5 to
30 minutes.
The in-suite signal silence timer expires, if programmed. See “What is in-suite signal
silence?on page 38 and on page 85.