Chapter 3: System operation
P/N 3102352-EN • REV 005 • ISS 28DEC18 155
• The disabled points indicator on the LCD decrements
• The active points indicator on the LCD decrements
To disable or enable the dialer and network card:
1. Press Remote Disconnect.
2. Enter a level one password.
Initiating a fire drill
Pressing Drill activates all audible and visible notification appliances according to the panel
programming, but does not activate the alarm relay.
Note: Drill does not operate when the panel has an active alarm or supervisory event.
To start a fire drill:
1. Press the Menu button and choose Control.
2. Enter a level one password.
3. Choose Drill.
The control panel turns on all notification appliance circuits.
To stop a fire drill:
1. Press the Menu button and choose Control.
2. Choose Drill.
The control panel turns off all notification appliance circuits.
Conducting a walk test
A walk test lets you test individual zones or devices without having to create an actual alarm
condition. You can conduct a walk test in silent or audible mode. In silent mode, the audible
devices (NACs) do not sound.
Zones should be placed in walk test one at a time. This allows the balance of the system to
remain in service. When a device is activated for testing, it remains active throughout the test
and does not restore until the walk test is ended. When the walk test is ended, all of the tested
devices restore.
Notes
• Walk test does not operate when the panel has an active alarm event.