Appendix C: Applications
P/N 3102352-EN • REV 005 • ISS 28DEC18 215
Programming sounder bases for a local alarm signaling
application
Note: For PD, PHD, and PDD detectors configured as “Supervisory Non-latching” device type
or for PCD detectors (smoke element) configured as “Smoke Supervisory Non-latching” device
type, if the base is Relay/Sounder, then the follow type option cannot be configured as “Head.”
The follow type in this case should be set to “Alarm.”
1. Set the panel’s Event Notification option to Device.
2. Configure the smoke detectors as follows.
Device Type: Smoke or Smoke Heat depending on the detector model
Message Line 1: Description of the installed detector location
Base Type: Sounder
Follow: Head
3. Configure the FX-NAC module as follows:
Device type: Supervised Output
Message Line 1: 24VDC_RISER
Message Line 2: SOUNDER_CKT_1