UL/ULC programming requirements
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND OTHER INVOLVED
PARTIES
This product incorporates field
-programmable software. In order for the product to comply with the requirements
of the listing agency, certain programming features or options must be limited to specific values or not used at all
as indicated below.
Programmable
feature or option
Possible settings Listing
Agency
Permitted
(Y/N)
Permitted
settings
Panel default
fail delay 0 to 15 hours UL, ULC Y 1 to 3 hours 3 hours