EasyManua.ls Logo

Kidde FX-64 - Panel Event Programming

Kidde FX-64
244 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 2: Front panel programming
P/N 3102352-EN • REV 005 • ISS 28DEC18 83
To remove all members from a correlation group:
1. Press the Menu button and choose Programming.
2. Choose Advanced Program and enter the level 2 password.
3 Choose Loop Configuration.
4. Choose Correlation Groups.
5. Enter the number of the correlation group. (Values range from 001 to 199.)
6. Choose Remove All. A warning message is displayed.
7. Choose Continue to remove all members from the group.
or
Press the Cancel button to return to the previous level without removing all members.
Note: Removing all members from a correlation group resets the activation count to 1 and
disables in-suite signal silence.
Adding and removing panel events
The following panel events can be added to correlation groups in order to trigger outputs in
that correlation. The outputs activate at the beginning of the event and restore when the events
restore.
Signal Silence
Drill
Common Alarm
Common Supervisory
Common Monitor
Common Disable
Common Trouble
Local AC Power
System AC Power
Aux Power 1
Aux Power 2

Table of Contents