Chapter 2: Front panel programming
38 P/N 3102352-EN • REV 005 • ISS 28DEC18
Circuit one on all FX-IDCWS modules
All FX-NAC modules
All panel NACs
All zones configured as alarm
The following inputs are not included in correlation group 001 during auto programming:
Relay and sounder bases with the Follow option set to Head. All sounder bases are
programmed as Relay during auto programming.
Addressable relays
Note the following:
Any items included in correlation group 001 can be removed manually using front panel
programming or the configuration utility.
Any detectors, modules, or zones, where the type is changed to a type other than alarm,
should be removed manually from correlation group 001 to avoid activating that correlation
group.
If zoning is used, the zones must be in the appropriate correlation group so devices
assigned to that zone activate the correlation group.
The CO elements for COD, PCD, HCD, and PHCD detectors are not included in
Correlation Group 1 during auto programming or auto zoning
What is in-suite signal silence?
In-suite signal silence is a form of automatic alarm silencing that can be enabled for correlation
groups. The function is used in residential complexes to minimize the annoyance of false
alarms within living quarters. When an alarm input device activates, evacuation signals
activate normally. After one minute, alarms in living quarters outside the alarm zone deactivate
briefly. This interval is called the shutdown period and gives building personnel time to
investigate the problem. Room evacuation signals in the alarm zone and hallway signals
throughout the building remain active.
If the alarm has not been cleared within programmed allotted time (1 to 10 minutes), or if a
subsequent alarm occurs, all signals resound. The shutdown period can be adjusted at the
panel. In-suite signal silence can be turned off completely at the panel by setting the Suite
Signal Silence option to Off (default). This setting is found at Program > Advanced Program >
Panel Operation.
In-suite signal silence is a feature commonly utilized in the Canadian marketplace. This feature
is not permitted when the system must meet UL 864 requirements for the US marketplace.
Notes
Only alarm events can initiate in-suite signal silence.