Chapter 4: Reports
162 P/N 3102352-EN • REV 005 • ISS 28DEC18
Device Maintenance report
The panel provides a Device Maintenance report of all detectors in the system. The report can
include: all detectors, all detectors over 20% dirty, or all detectors over 80% dirty. The report
displays the device, along with its dirty percentage and sensitivity setting. Device Maintenance
reports can be printed or viewed on the LCD.
Note: On an unconfigured system with a full load of CO devices, after the system has been
configured, it takes approximately 1.5 hours to retrieve the CO running days data from all
devices. For subsequent restarts,without reprogramming, the delay in reporting the running
days is less than 5 minutes.
To view a Device Maintenance report:
1. Press the menu button and choose Reports.
2. Choose Device Maintenance.
3. Choose one of the following:
All Devices
Devices >= 20% Dirty
Devices >= 80% Dirty.
Note: COD, HCD, PCD, and PHCD detectors have a lifespan of ten years. They report the
number of months left until end of life on the LCD and in maintenance reports. When a CO
detector has less than six months until EOL, the LCD displays a maintenance alert. When the
months until EOL reach zero, the LCD restores the maintenance alert and issues an EOL
trouble for the device. For combination detectors, the system detects and reports the percent
dirty separate from the CO number of months until EOL.
System Status report
The panel provides a System Status report for all active points in the system. The report can
include: all active points, all alarm points, all supervisory points, all trouble points, all disabled
points, or all other points. System status reports can be printed or viewed on the LCD.
To view a System Status report:
1. Press the Menu button and choose Reports.
2. Choose System Status.
3. Choose one of the following:
All
Alarm