Kidde FX-64 - Programming Sounder Bases for a Local Alarm Signaling Application

Kidde FX-64
244 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Appendix C: Applications
222 P/N 3102352-EN • REV 005 • ISS 28DEC18
Programming sounder bases for a local alarm signaling
application
Note: For PD, PHD, and PDD detectors configured as “Supervisory Non-latching” device type
or for PCD detectors (smoke element) configured as “Smoke Supervisory Non-latching” device
type, if the base is Relay/Sounder, then the follow type option cannot be configured as “Head.”
The follow type in this case should be set to “Alarm.”
To program sounder bases for local alarm signaling:
1. Set the panel’s Event Notification option to Device.
2. Configure the smoke detectors as follows:
Message Line 1: Description of the installed detector location
Base: Sounder
Follow: None, Alarm, Alm + Vrfy, or Alm + PreAlm
3. Configure the RLY module as follows:
Device Type: Relay Silence
Message Line 1: SOUNDER_RLY_1
4. Configure the FX-NAC module as follows:
Device type: Supervised Output
Message Line 1: 24VDC_RISER
Message Line 2: SOUNDER_RLY_1
5. Configure Correlation 001 as follows:
Add/Remove Device: All alarm signal-initiating devices
Add/Remove NAC: All RLY modules used to active sounder bases