Chapter 3: System operation
P/N 3102352-EN • REV 005 • ISS 28DEC18 137
Event ID numbers and descriptions
Table 45: Event ID numbers and descriptions
ID
Event description
000
Loop 1 initialization: Loop 1 is
starting up
001
Loop 1 fault: A short or open was
detected on loop 1 affecting the
communications between the panel
and the devices on the loop
002
Not used
003
Loop 1 card fault: The loop 1 card is
not present or it is not working
properly
004
Loop 1 uncfgrd alarm: A device on
loop 1 that is not programmed went
into alarm
005
Loop 1 uncfgrd trouble: A device on
loop 1 that is not programmed went
into trouble
006
Not used
007
Loop 1 over limits: There are too
many devices on loop 1
008
Loop 1 device 000: A device on loop
1 has an address set to zero
009
Not used
010
Loop 2 initialization: Loop 2 is
starting up
011
Loop 2 fault: A short or open was
detected on loop 2 affecting the
communications between the panel
and the devices on the loop
012
Not used
013
Loop 2 card fault: The loop 2 card is
not present or it is not working
properly
014
Loop 2 uncfgrd alarm: A device on
loop 2 that is not programmed went
into alarm
015
Loop 2 uncfgrd trouble: A device on
loop 2 that is not programmed went
into trouble
ID
Event description
016
Not used
017
Loop 2 over limits: There are too
many devices on loop 2
018
Loop 2 device 000: A device on loop
2 has an address set to zero
019
Not used
020
Loop 3 initialization: Loop 3 is
starting up
021
Loop 3 fault: A short or open was
detected on loop 3 affecting the
communications between the panel
and the devices on the loop
022
Not used
023
Loop 3 card fault: The loop 3 card is
not present or it is not working
properly
024
Loop 3 uncfgrd alarm: A device on
loop 3 that is not programmed went
into alarm
025
Loop 3 uncfgrd trouble: A device on
loop 3 that is not programmed went
into trouble
026
Not used
027
Loop 3 over limits: There are too
many devices on loop 3
028
Loop 3 device 000: A device on loop
3 has an address set to zero
029
Not used
030
Loop 4 initialization: Loop 4 is
starting up
031
Loop 4 fault: A short or open was
detected on loop 4 affecting the
communications between the panel
and the devices on the loop
032
Not used