Chapter 3: System operation
138 P/N 3102352-EN • REV 005 • ISS 28DEC18
ID
Event description
033
Loop 4 card fault: The loop 4 card is
not present or it is not working
properly
034
Loop 4 uncfgrd alarm: A device on
loop 4 that is not programmed went
into alarm
035
Loop 4 uncfgrd trouble: A device on
loop 4 that is not programmed went
into trouble
036
Not used
037
Loop 4 over limits: There are too
many devices on loop 4
038
Loop 4 device 000: A device on loop
4 has an address set to zero
039
Not used
040
System startup: The control panel is
starting up
041
Program mode: The control panel is
in program mode
042
Reset: The control panel is resetting
043
Reset/Sil inhibit: Reset/silence inhibit
is activated
044
Panel silence: The control panel
buzzer was silenced
045
Signal silence: The control panel
NACs have been silenced
046
Drill: The control panel is in the drill
state
047
Walk test: The control panel is in the
walk test state
048
Test fire: A smoke or heat detector is
being tested
049
Clear history: The control panel’s
event history was cleared
050
Time: The control panel’s time was
modified
051
Date: The control panel’s date was
modified
052
Common disable: A disable event is
taking place on the control panel
ID
Event description
053
Common trouble: A trouble event is
taking place on the control panel
054
Ground fault: The panel detected a
ground fault
055
Battery charger: The panel detected
a battery charger trouble condition.
The charger may not be able to
charge the batteries.
056
Battery low: The batteries are low on
charge
057
Battery missing: The battery is no
longer connected
058
AC power: There is a problem with
the panel’s AC power
059
Aux. power 1: The control panel
detected a trouble condition on the
continuous AUX power circuit 1
060
Aux. power 2: The control panel
detected a trouble condition on the
resettable AUX power circuit 2
061
System AC power: There is a
problem with the panel’s AC power
and/or a remote auxiliary/booster’s
AC power
062
Common alarm: An alarm event is
taking place on the control panel
063
Common supervisory: A supervisory
event is taking place on the control
panel
064
Common monitor: A monitor event is
taking place on the control panel
065
Common trouble for telco dialer: A
trouble event, other than a DACT
delivery fault is taking place on the
control panel
066
Common trouble for network dialer:
A trouble event, including a DACT
delivery fault is taking place on the
control panel
067
Outputs Are Latched: Outputs in the
system are in latched condition
068
Alarm ON:
The control panel is in the
manual evacuation state.