Chapter 2: Front panel programming
82 P/N 3102352-EN • REV 005 • ISS 28DEC18
Setting a correlation group’s activation count
A correlation group’s activation count is the number of member activations that are required to
activate the correlation group. The activation count is used to set up cross zoning. The
following rules apply:
• The count cannot exceed the number of input members in the correlation group
• The default value is 1
• Input members can be zones, NACs, devices, unconfigured alarm events, or the common
trouble event
• The activation count must be 1 for correlation groups with in-suite signal silence enabled
• The activation count must not exceed 2 for cross zoning applications and the zones should
not have alarm verification per ANSI/NFPA 72-2002 6.8.5.4.3
To set the activation count:
1. Press the Menu button and choose Programming.
2. Choose Advanced Program and enter the level 2 password.
3 Choose Loop Configuration.
4. Choose Correlation Groups and enter the number of the correlation group to be
programmed. (Values range from 001 to 199.)
5. Choose Activation Count and enter the activation count (values range from 01 to 99).
6. Choose Save.
To copy the members of a correlation group:
1. Press the Menu button and choose Programming.
2. Choose Advanced Program and enter the level 2 password.
3 Choose Loop Configuration.
4. Choose Correlation Groups.
5. Enter the number of the correlation group to be programmed. (Values range from 001 to
199.)
6. Choose Copy and enter the number of the correlation group to be copied.
7. Choose Save.