Chapter 2: Front panel programming
P/N 3102352-EN • REV 005 • ISS 28DEC18 81
2. Choose Advanced Program and enter the level 2 password.
3. Choose Correlation Groups and enter the correlation group number to be programmed.
(Values range from 001 to 199.)
4. Choose:
• Add/Remove Zone to add or remove a zone
• Add/Rem Panel NAC to add or remove a NAC
• Add/Rem Device to add or remove a device
Note: The Add/Rem device includes primary sensor, secondary sensor, and base, if
applicable.
• Add/Rem Panel Event
• Suite Sig Sil
• Activation Count
• Delay
• Copy
• Remove All
• Save
5. Enter the loop number (if the panel has multiple loops).
6. Enter the zone, NAC, or device number.
7. On the Status line, press Enter to select Included or Excluded:
• “Included” adds the item to the group
• “Excluded” removes the item from the group
8. Repeat steps 4 to 7 to add or remove other devices, zones, or NACs.
9. Repeat steps 3 to 9 to program additional correlation groups.
10. Press the Menu button to exit menu mode, or continue programming.
To add the Common Trouble Event to a correlation group:
1. Press the Menu button and choose Programming.
2. Choose Advanced Program and enter the level 2 password.
3. Choose Common Trouble then choose Trouble.
4. Choose Correlation Groups and enter the number of the correlation group to be configured.
5. Press Enter to toggle between possible values:
• “Included” adds the item to the group
• “Excluded” removes the item from the group
6. Repeat steps 7 to 9 to add or remove the event from any remaining correlation groups to
be configured.
7. Choose Save.
8. Press the Menu button to exit menu mode or continue programming.