Chapter 2: Front panel programming
P/N 3102352-EN • REV 005 • ISS 28DEC18 93
Selecting loop classes
The loop class must be programmed Class A or Class B based on how the devices are wired
on the loop). The default setting is Class B.
To select a loop class:
1. Press the Menu button and choose Programming.
2. Choose Advanced Program and enter the level 2 password.
3. Choose Loop Class.
4. Select the loop. If you only have one loop, the loop is automatically selected.
5. Select either Class A or Class B.
6. Choose Save.
7. Press the Menu button to exit menu mode, or continue programming.
Zone programming
Notes
• For background information about zones, see “What is a zone?” on page 36.
• If the system does not have zones, no programming is required in this section. If the panel
is not configured for zone or zone/device reporting, programming here has no effect on the
system except for CMS reporting.
Table 31: Zone programming options
Set the zone type to one of the following values.
Alarm: For circuits with smoke detectors and contact devices. All activations
are immediately considered as alarms. Circuit cannot be restored until devices
are restored to normal and panel is reset.
Monitor: Monitoring of normally open switches for other functions (fire door
position, etc.). Not approved for use under CAN-ULC-S527 in Canada.
Supervisory: For supervisory devices. Momentary activation of normally open
devices immediately places the panel in a supervisory state and turns on the
supervisory LED and relay.
The device types of the devices in a supervisory zone determine whether the
zone is latching or nonlatching. If all devices in the zone are latching devices,
or if you mix latching and nonlatching devices, the zone will operate as
latching.
Waterflow: Activates alarm events when a waterflow switch closes. Select this
zone type when the devices in the zone are only connected to waterflow
switches.