Chapter 2: Front panel programming
92 P/N 3102352-EN • REV 005 • ISS 28DEC18
Description
Relay nonsilence NC (latched)
Relay NC Latch. For relay devices functioning as latched
outputs that open when activated. Does not follow signal
silence.
To configure a relay module or base as a latched output:
1. Press the Menu button and choose Programming.
2. Choose Advanced Program and enter the level 2 password.
3. Choose Loop Configuration.
4. Choose Device.
5. If the panel has multiple loops, choose the loop to be configured.
6. Enter the device address to be configured. Device details are displayed.
7. Set the Base Type option to Relay.
8. Set the Follow option to None.
9. Set the Latched option to Yes.
10. Choose Type and select one of the Latched Outputs types listed in Table 29 on page 91.
11. Press the Menu button to exit menu mode, or continue programming.
Loops 1, 2, 3, and 4 mapping enable
If your system is using multiple device loops, you must enable loops 1, 2, 3, or 4 so that they
can be programmed.
To enable loops 1, 2, 3, or 4:
1. Press the Menu button and choose Programming.
2. Choose Advanced Program and enter the level 2 password.
3. Choose Loop Configuration.
4. Choose Loop 1, 2, 3, or 4 Enable.
5. Select:
Yes to enable the selected loop
No to disable the selected loop
6. Repeat steps 3 and 4 for each loop you want to enable.
7. Choose Save.
8. Press the Menu button to exit menu mode, or continue programming.