Chapter 2: Front panel programming
68 P/N 3102352-EN • REV 005 • ISS 28DEC18
Dialer options
Table 23 describes the options used to set up the dialer.
Table 23: Auto programming Dialer options [1]
Option Description
Account 1
Account ID: Enter the four-digit ID code for account 1 Note, if you do not change the
default of FFFF, no events will be sent.)
Primary receiver number: Enter the primary receiver’s phone number. Up to 20 digits (0-9,
*, #, and ,). The comma causes a two-second delay in dialing. The number or hash symbol
(#) and the asterisk symbol (*) are used with calling feature codes and services. Consult
your telephone service provider.
Secondary receiver number: Enter the secondary receiver’s phone number. Up to 20 digits
(0-9, *, #, and ,). The comma causes a two-second delay in dialing.
Format: CID
CID: Contact ID is the alarm format that the monitoring facility (DACR) will receive. See
Default contact ID event codeson page 45.
Event notification: Set event notification (event reporting) to:
Device: Only device information is reported or transmitted, no zone information. This
setting uses default device event notification settings for reporting events. SeeFactory
default settingson page 41.
Zone: When a device is a member of a zone, only the zone information is reported or
transmitted, no device information. This setting uses default zone event notification
settings for reporting events. See “Factory default settingson page 41.
Event: Only the event type (alarm, supervisory, trouble, etc.) is reported or transmitted, no
device or zone information. This setting uses the default CMS event notification settings
for reporting events. See “Factory default settingson page 41.
Account 2 Account ID: Enter four-digit ID code for account 2.
Primary receiver number: Enter the primary receiver’s phone number (up to 20 digits).
Secondary receiver number: Enter the secondary receiver’s phone number (up to 20
digits).
Format: CID
CID: Contact ID is the alarm format that the monitoring facility (DACR) will receive. See
Default contact ID event codeson page 45.
Event notification: Set event notification (event reporting) to:
Device: Only device information is reported or transmitted, no zone information. This
setting uses default device event notification settings for reporting events. SeeFactory
default settingson page 41.
Zone: When a device is a member of a zone, only the zone information is reported or
transmitted, no device information. This setting uses default zone event notification
settings for reporting events. See “Factory default settingson page 41.
Event: Only the event type (alarm, supervisory, trouble, etc.) is reported or transmitted, no
device or zone information. This setting uses the default CMS event notification settings
for reporting events. See “Factory default settingson page 41.
[1] Dialer options are displayed only if a dialer is installed on the panel.