Chapter 2: Front panel programming
P/N 3102352-EN • REV 005 • ISS 28DEC18 99
Description
• Acct 1: Event information is sent to dialer account one
• Acct 2: Event information is sent to dialer account two
• None: Event information is not sent to the dialer
CID: Contact ID event code (000 to 999)
NET (1-8): Yes or No. Controls whether event information is sent to the
connected network
To program an annunciator:
1. Press the Menu button and choose Programming.
2. Choose Advanced Program and enter the level 2 password.
3. Choose Panel Configuration.
4. Choose Annunciator.
5. Choose the annunciator you want to program.
6. Program each annunciator in the system using Table 33 on page 98.
7. When you finish programming each option, choose Save.
8. Press the Menu button to exit menu mode, or continue programming.
Central monitoring station device programming
CMS device programming
CMS devices are the devices that transmit system events to a central monitoring station’s
receiver. This includes the dialer and the network.
Table 34: CMS device options
Description
See “Dialer programming” on page 101.
shutdown Set swinger shutdown to Off or 1 to 255 repetitions. When you have
finished, press Enter to save.
Note: Off is the only acceptable setting for UL/ULC installations. See
“UL/ULC programming requirements” on page 34 for details.
This automatically inhibits the number of consecutive times a single trouble
event is transmitted over a 24-
hour period before it is no longer sent. Some
trouble events are not affected when swinger shutdown is set. They are:
- Loop 1 initializing
- Loop 1 uncfgrd alarm
- Loop 1 over limits
- Loop 4 device 000
- System startup