Chapter 2: Front panel programming
98 P/N 3102352-EN • REV 005 • ISS 28DEC18
Setting annunciator classes
Program the annunciator’s wiring class (Class A or Class B). You must install the optional SA-
CLA module if you have class annunciator wiring on the 64 point panel.
Default: Class B
To set the annunciator class:
1. Display the panel configuration options menu. See “Panel programming” on page 95.
2. Choose Ann. Class.
3. Select either Class A or Class B.
4. Program other panel configuration options or choose Save if you’re finished.
5. Press the Menu button to exit menu mode, or continue programming.
Annunciator programming
Each annunciator on the annunciator loop must be programmed for type, number of
expanders, label, and event notification. Up to eight annunciators can be connected on the
loop and each must be programmed separately. You must also set the address on each
annunciator by using the DIP switch on the back of the annunciator.
Table 33: Annunciator options
Description
Set annunciator type to:
Off: No annunciator is connected. If type is set to Off, Number expanders,
Label, and Reporting configuration are not available.
LCD-C: The annunciator has a display and common controls
LCD: The annunciator has a display only (no common controls)
LED: The annunciator has LEDs and common controls (no display)
Graphic: Graphics controller interface for the third-party LED graphic
annunciator
Set expanders to None, 1, or 2. This is the number of LED expander modules
you are using with the annunciator.
Enter a text label for the annunciator (two lines of 20 characters). When you
have finished, choose Save.
Set the trouble event information by setting the notification information. When
you have finished, choose Save. See “Factory default settings” on page 41
for annunciator event notification default settings.
Printer: Yes or No. This controls whether event information is sent to the
printer
Dialer:
• Acct 1 & 2: Event information is sent to both dialer accounts