Chapter 2: Front panel programming
100 P/N 3102352-EN • REV 005 • ISS 28DEC18
Option
Description
- Loop 1 device 000
- Loop 2 initializing
- Loop 2 over limits
- Loop 2 uncfgrd alarm
- Loop 2 device 000
- Loop 3 initializing
- Loop 3 uncfgrd alarm
- Loop 3 over limits
- Loop 3 device 000
- Loop 4 initializing
- Loop 4 uncfgrd alarm
- Reset
- Reset/Sil inhibit
- Panel silence
- Program mode
- Signal silence
- Date - Drill
- Walk test
- Test fire
- Time
- Clear history
- Common alarm
- Common disable
- Common monitor
- Common supervisory
- Common trouble
- Battery charger
- Battery low
- Battery missing
- Local AC power
- System-wide AC power
- Self test fault
- Dialer dsbl/rem disc
- Dialer normal test
- Dialer abnormal test
- Dialer configuration
Event notification
Note: Programming event notification here is only required if you selected
“Event” as your dialer account or network event notification setting. See
Dialer programmingon page 101.
Set the alarm, supervisory, monitor, trouble, disable, prealarm, alarm
verify, maintenance alert, and test event information by choosing one and
then setting the notification information. When you have finished, choose
Save. See Factory default settingson page 41 for CMS device event
notification default settings.
Dialer:
Acct 1 & 2: Event information is sent to both dialer accounts
Acct 1: Event information is sent to dialer account one
Acct 2: Event information is sent to dialer account two
None: Event information is not sent to the dialer
NET (1-8): Yes or No. Controls whether event information is sent to the
connected network
CID: Contact ID event code (000 to 999)