Chapter 2: Front panel programming
P/N 3102352-EN • REV 005 • ISS 28DEC18 35
Programmable
feature or option
Possible settings Listing
Agency
Permitted
(Y/N)
Permitted
settings
Panel default
Telephone line cut
supervision duration
1 to 120 seconds UL, ULC Y 10 to 120 seconds 120 seconds
Transmission test
frequency
0 to 240 hours UL
ULC
Y
Y
6 hours
24 hours
6 hours
6 hours
Auto signal
silence Off or 5 to 30 minutes UL
ULC
Y
N
5 to 30 minutes
Off
Off
Dialer mode
Dual line
Single line
Modem only
None
UL, ULC Y Dual line
Single line [2]
Modem only [3]
None [3]
Dual line
Dialer retries
5 to 10 UL, ULC Y 5 minimum 5 retries
Dialer retry
time 1 to 45 seconds UL, ULC Y Yes 5 seconds
Send event restore
codes [1]
No or Yes UL, ULC Y Yes Yes
Swinger shutdown
Off or 1 to 255 UL, ULC N Off Off
Zone resound
On or Off UL, ULC Y On On
Carbon monoxide (CO)
signaling
CO signaling
correlation
Input: (CO element of
the detector):
CO Alarm
CO Supervisory
CO Monitor
Output: Channel 2 of
T3T4 module
UL, ULC Y Input: (CO element
of the detector) [4]:
CO alarm
Output: Channel 2
of T3T4 module
No default
correlation
CO detector with a
CO alarm device
type
Zone event
notification Type
Alarm, Monitor,
Supervisory, Waterflow
Alarm, Monitor,
Supervisory, Waterflow
UL
ULC
Y
Y
Alarm, Monitor,
Supervisory,
Waterflow
Supervisory [5]
Alarm
Alarm
[1] Allowed only if the IDC is connected to the latching alarm device
[2] Allowed only when the supervising station supervises the telephone line and annunciates fault conditions
within 200 seconds
[3] Prohibited when the control panel is connected to a supervising station
[4] CO alarm signals are required to activate TC4 CO evacuation signals but CO Supervisory or CO Monitor
signals are not allowed to activate CO evacuation signals. CO alarm/CO supervisory/CO monitor signals shall not
activate TC3 fire evacuation signals.