Appendix C: Applications
P/N 3102352-EN • REV 005 • ISS 28DEC18 217
The FX-NAC is used to supervise the 24 VDC riser only. When using the FX-NAC as a
riser supervision module, it cannot be used for notification appliances or included in a
correlation group.
The following procedure must be done using the Configuration Utility (CU).
To program the sounder base for T3T4 Fire/CO:
1. Configure the detectors as follows:
Message Line 1: Description of the installed detector location
Device Type: Primary sensor type + CO alarm
Base Type: Sounder
Follow: None, Head, Alarm, Alm + Vrfy, or Alm + PreAlm
Follow CO: No or Yes (only displays if Follow is set to Alarm, Alm + Vrfy, or Alm + PreAlm)
2. Configure the FX-NAC module as follows:
Device type: Supervised Output
Message Line 1: 24VDC_RISER
Message Line 2: SOUNDER_CKT_1
3. Configure Correlation Group 001 as follows:
Add/Remove Zone: As required
Add/Remove NAC: As required
Add/Remove Device: Add all alarm signal initiating devices corresponding T3T4 device
Channels as described below
To create correlations for T3T4:
1. Channel 1 must be correlated with proper sounder base as output to any primary alarming
type inputs.
2. Channel 2 can be correlated with proper sounder base as output to secondary element
(CO) of detectors.
3. If both Channel 1 and Channel 2 are correlated as outputs to a sounder base, then
Channel 1 pattern overwrites the Channel 2 pattern.
Notes
Channel 1: T3T4-TC3 (fire): The device at address visible on T3T4 device.
Channel 2: T3T4-TC4 (CO): The device at address above plus one.
CO alarm signals are required to activate TC4 CO evacuation signals. CO supervisory or
CO monitor signals are not allowed to activate CO evacuation signals.