Appendix A: Panel specifications
P/N 3102352-EN • REV 005 • ISS 28DEC18 181
FX-64 panel FX-1000 panel
Loop circuit
Maximum loop resistance: 66 Ω
Maximum loop capacitance: 0.5 µF
Communication line voltage: Maximum 20.6 V peak-to-peak
Operating current (fully loaded loop)
Stand by: 55 mA/45 mA
Alarm: 125 mA/115 mA (this does not include two-wire smoke modules)
Circuit current: 0.5 A max.
Max. resistance between isolators: Limited only by overall wire run lengths
64 isolators maximum per loop (total both isolator bases and modules)
Batteries
Type: Sealed lead acid
Voltage: 24 VDC
Charging current: 2.47 A max.
Amp hour capacity: 26 Ah
Standby operation: 24 hour or 60 hour
Placement: Up to two 10 Ah batteries will fit in the FX-64 control panel cabinet and
two 18 Ah batteries will fit in the FX-1000
control panel cabinet. If larger batteries are
required, you must use an Edwards battery cabinet.
SA
-DACT dialer Phone line type: One or two loop-start lines on a public, switched network
Phone line connector: RJ-31/38X (C31/38X)
Communication formats: Contact ID (SIA DC-05)
Operating current
Standby/Alarm: 41 mA
Max.: 100 mA
FCC registration number: GESAL01BSADACT
Industry Canada Registration number: 3944A-SADACT
Ringer equivalence number: 0.1B
Ground fault impedance
0 to 5 kΩ
Alarm contact
Class E, Form C N.O. 24 VDC at 1 A (resistive load)
Trouble contact
Class E, Form C 24 VDC at 1 A (resistive load)
Supervisory contact
Class E, Form A N.O. 24 VDC at 1 A (resistive load)
Environmental
Temperature: 0 to 49°C (32 to 120°F)
Relative humidity: 0 to 93% noncondensing
Terminal rating
All terminals rated for 12 to 18 AWG (0.75 to 2.5 m)

Table of Contents