Control terminals
With function "Safe torque off" deactivated
5.6
5.6.4

5.6−8
EDSVF9383V EN 7.1−04/2012
Supply via external voltage source
GND2 +24V+5 V
E5
A2 A3 A4 ST1
ST2
59
39
3k
47k
50mA
50mA
50mA
50mA
X5
28
E1 E2 E3 E4
3k
3k
3k
3k
3k
DC 24 V
(+18 V … +30 V)
X11
K31K32 33 34
S1
+
K
SR
+
–
A1
X3
GND1 GND1
X6
12
3
4
7762
63
242R
1
2
3
4
5
6
100k
100k
100k
100k
3.3nF
AIN1 AIN2
AOUTx
AOUT2
AOUT1
1
3
247
10k 10k
9300vec138
Fig. 5.6−6 Wiring of digital and analog inputs/outputs with function "Safe torque off"
deactivated, given an external voltage source
S1 Controller enable
NO contact or NC contact
Z
Load
Minimum wiring required for operation
Terminal assignment in the Lenze setting:  5.6−9
 Note!
Supplying the digital inputs via an external voltage source
enables a backup operation in the case of mains failure. After
switching off the mains voltage, all actual values are continued
to be detected and processed.
Æ’ Connect the positive pole of the external voltage source with
X5/59 to establish the backup operation in the event of mains
failure.
Æ’ The external voltage source must be able to supply a current
³ 1 A.
Æ’ The starting current of the external voltage source is not
limited by the controller. Lenze recommends the use of
voltage sources with current limitation or with an internal
impedance of Z > 1 W.

Table of Contents

Other manuals for Lenze EVS9321-Ex

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lenze EVS9321-Ex and is the answer not in the manual?

Lenze EVS9321-Ex Specifications

General IconGeneral
BrandLenze
ModelEVS9321-Ex
CategoryController
LanguageEnglish

Related product manuals