Operating mode
Vector control
6.8
6.8.2

6.8−10
EDSVF9383V EN 7.1−04/2012
C0006 = 1 set the vector control mode.
 Note!
When setting the vector control mode, the slip compensation
(C0021) is automatically set to 0.0 %.
Æ’ When you switch back to the V/f characteristic control mode,
the slip compensation must be re−adapted.
The motor data of the motor nameplate must be entered:
Æ’ Rated motor speed (C0087)
Æ’ Rated motor current (C0088)
Æ’ Rated motor frequency (C0089)
Æ’ Rated motor voltage (C0090)
Æ’ Motor cos j (C0091)
Execute the motor data identification. (
 6.6−15)
Set vector control
Prepare the motor data
identification
Executing the motor data