8400 BaseLine D | Software Manual
Parameter reference
Parameter list | C00517
206 L Firmware 03.00 - DMS EN 5.0 - 07/2009
C00517
C00565
C00574
Parameter | Name:
C00517 | User menu
Data type: INTEGER_32
Index: 24058
d
= 5DFA
h
When a system is installed, parameters must be changed time and again until the system runs satisfactorily. The
user menu of a device serves to create a selection of frequently used parameters to be able to access and change
these parameters quickly.
Setting range (min. value | unit | max. value)
0 994
Subcodes Lenze setting Info
C00517/1 51 C00051
: Display of actual speed value
C00517/2 53 C00053
: Display of DC-bus voltage
C00517/3 54 C00054
: Display of motor current
C00517/4 61 C00061
: Display of heatsink temperature
C00517/5 137 C00137
: Display of device state
C00517/6 0
C00517/7 0
C00517/8 11 C00011
: Reference speed
C00517/9 39 C00039
: Fixed setpoints 1 ... 3
C00517/10 0
C00517/11 12 C00012
: Accel. time - main setpoint
C00517/12 13 C00013
: Decel. time - main setpoint
C00517/13 15 C00015
: V/f base frequency
C00517/14 16 C00016
: Vmin boost
C00517/15 22 C00022
: Imax in motor mode
C00517/16 120 C00120
: Motor overload threshold (I
2
xt)
C00517/17 87 C00087
: Rated motor speed
C00517/18 99 C00099
: Display of firmware version
C00517/19 0
C00517/20 0
; Read access ; Write access CINH PLC STOP No transfer COM MOT Scaling factor: 1
Parameter | Name:
C00565 | Resp. to mains phase failure
Data type: UNSIGNED_8
Index: 24010
d
= 5DCA
h
Response to the failure of mains phases
Selection list (Lenze setting printed in bold)
0 No Reaction
1Fault
4 WarningLocked
; Read access ; Write access CINH PLC STOP No transfer COM MOT Scaling factor: 1
Parameter | Name:
C00574 | Resp. to brake resist. overtemp.
Data type: UNSIGNED_8
Index: 24001
d
= 5DC1
h
Response to overtemperature of the brake resistor
Selection list (Lenze setting printed in bold)
0No Reaction
1Fault
4 WarningLocked
; Read access ; Write access CINH PLC STOP No transfer COM MOT Scaling factor: 1