EasyManua.ls Logo

Link4 iPonic 600 - CO2 Global Settings; CO2 Setpoint

Link4 iPonic 600
72 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
960-0001-20 iGrowSeries 100 Installation and User Manual 25
1.3 CO2 SetPoint
The CO2 setpoint is the threshold below which the CO2
injection will be enabled. Use the wheel to increase or
decrease the setpoint value.
Press #7 to set the Day and Night start times.
Press #8 to go to the Global CO2 settings screen.
If the Night CO2 setpoint is ON, then you will see this screen.
Press #5 to toggle between enabling the Night CO2 setpoint
or disabling it.
The night threshold functions the same as the day setpoint
described above.
This is the display you will get when you turn the CO2 night or
the DIF setpoints Off.
Pressing #5 will turn it back On.
1.3.1 CO2 Global Settings
DeadBand: This is the number of PPM that the CO2 must
drop below the Setpoint before CO2 injection is resumed.
Press #1 to set the CO2 deadband
There are a few conditions that will override the CO2 injection
process:
CO2 cut off: If enabled, the controller will not inject CO2 into
the grow room if the lights are turned off. There are two ways
that the controller determines whether or not the lights are off:
a. Using the "light controls". In this case, the controller is
controlling the lights. So whenever the lights output (usually
#1) are off, the CO2 injection process stops.
b. Using the light sensor/meter. In this case, the controller
is probably not controlling the lights. The controller will use
the light sensor on the sensor module to detect if the lights are
off or not. It has two parameters: light threshold and