EasyManuals Logo

LSIS sv-ig5a User Manual

LSIS sv-ig5a
186 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #145 background imageLoading...
Page #145 background image
9-11
12: During operation
Activated when run command is input and inverter outputs its voltage.
13: During stop
Activated during stop without active command.
14: during constant run
Activated during constant speed operation.
15: During speed searching
Refer to page 8-17.
16: Wait time for run signal input
This function becomes active during normal operation and that the inverter waits for
active run command from external sequence.
17: Fault output
The parameter set in I56 is activated.
For example, if setting I55, I56 to 17 and 2, respectively, Multi-function output relay
will become active when trip other than Low voltage trip occurred.
18: Cooling fan trip alarm
Used to output alarm signal when H78 is set to 0(constant operation at cooling fan
trip). Refer to page 8-31.
19: Brake signal
It is used for signal output when set for use of external brake signal. Refer to the page
8-26.
Freq.
MO
Run
command
Freq.
MO
Run
command
Freq.
MO
Run
command
For Service Call 800-848-2504
For Service Call 800-848-2504

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the LSIS sv-ig5a and is the answer not in the manual?

LSIS sv-ig5a Specifications

General IconGeneral
BrandLSIS
Modelsv-ig5a
CategoryInverter
LanguageEnglish

Related product manuals