4) Action Request for monitor register: Request for read of address registered by monitor register.
ENQ
Drive No
CMD
SUM
EOT
05h
01 ~ 1F
Y
XX
04h
1 byte
2 bytes
1 byte
2 bytes
1 byte
Total bite = 7
4.1) Acknowledge response:
ACK
Drive No
CMD
Data
SUM
EOT
06h
01 ~ 1F
Y
XXXX…”
XX
04h
1 byte
2 bytes
1 byte
n * 4 bytes
2 bytes
1 byte
Total bite= 7 + n * 4 = Max 39
4.2) Negative response:
NAK
Drive No
CMD
Error code
SUM
EOT
15h
01 ~ 1F
Y
**
XX
04h
1 byte
2 bytes
1 byte
2 bytes
2 bytes
1 byte
Total bite = 9
5) Error code
Error code
Description
IF
When master is sending codes other than Function code (R, W, X, Y).
IA
When parameter address does not exist
ID
When Data value exceeds its permissible range during W (Write).
WM
When the specific parameters cannot be written during W (Write).
(For example, in the case of Read Only, Write disabled during Run)
FE
When frame size of specific function is not correct and Checksum field is
wrong.
11.7 Parameter code list <Common area> (Note1)
<Common area>: Area accessible regardless of inverter models (Note 2)
Address
Parameter
Scale
Unit
R/W
Allotment for Bits
0x0000
Inverter model
-
-
R
A : iG5A
0x0001
Inverter capacity
-
-
R
FFFF :
0.4kW
0000 :
0.75kW
0002 :
1.5kW
0003 :
2.2kW
0004 :
3.7kW
0005 :
4.0kW
0006 :
5.5kW
0007 :
7.5kW
0008 :
11kW
0009 :
15kW
000A :
18.5kW
000B :
22kW
For Service Call 800-848-2504
For Service Call 800-848-2504