3-2
3.2 Recommended MCCB
Inverter
Capacity
MCCB
LS
MC
Inverter
Capacity
MCCB
LS
MC
004iG5A-1
TD125U,EBs33
GMC-9
004iG5A-4
TD125U,EBs33
GMC-9
008iG5A-1
TD125U,EBs33
GMC-9
008iG5A-4
TD125U,EBs33
GMC-9
015iG5A-1
TD125U,EBs33
GMC-12
015iG5A-4
TD125U,EBs33
GMC-9
004iG5A-2
TD125U,EBs33
GMC-9
022iG5A-4
TD125U,EBs33
GMC-12
008iG5A-2
TD125U,EBs33
GMC-9
037iG5A-4
TD125U,EBs33
GMC-18
015iG5A-2
TD125U,EBs33
GMC-12
040iG5A-4
TD125U,EBs33
GMC-22
022iG5A-2
TD125U,EBs33
GMC-18
055iG5A-4
TD125U,EBs33
GMC-32
037iG5A-2
TD125U,EBs33
GMC-32
075iG5A-4
TD125U,EBs33
GMC-32
040iG5A-2
TD125U,EBs33
GMC-32
110iG5A-4
TD125U,EBs53
GMC-40
055iG5A-2
TD125U,EBs53
GMC-40
150iG5A-4
TD125U,EBs53
GMC-50
075iG5A-2
TD125U,EBs53
GMC-50
185iG5A-4
TD125U,EBs53
GMC-65
110iG5A-2
TD125U,EBs53
GMC-65
220iG5A-4
TD125U,EBs53
GMC-65
150iG5A-2
TD125U,EBs53
GMC-100
185iG5A-2
TS250U,EBs53
GMC-100
220iG5A-2
TS250U,EBs53
GMC-125
Note
1. The capacity of the MCCB should be 1.5 to 2 times the rated output current of the drive.
2. Use an MCCB keep the drive from faulting out instead of using overheat protection (150% for one
minute at the rated output current.)
3. In case magnetic contactor is used on single-phase product, wire R and T phases.
For Service Call 800-848-2504
For Service Call 800-848-2504

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the LSIS sv-ig5a and is the answer not in the manual?

LSIS sv-ig5a Specifications

General IconGeneral
BrandLSIS
Modelsv-ig5a
CategoryInverter
LanguageEnglish

Related product manuals